Clapboard: | without Clapboard |
---|---|
Filter Number: | 5 |
Medium Material: | PP |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | FFU-2*2 | FFU-2*4 | FFU-4*4 | |
Module size(W x L x H) | 575*575*250mm | 1175*575*250mm | 1175*1175*250mm | |
Air flow | 900 | 1000 | 1200 | |
Average velocity(m/s) | 0.3-0.5 | 0.3-0.5 | 0.3-0.5 | |
Pressure(pa) | 97(10mmAq) | 97(10mmAq) | 97(10mmAq) | |
Power(W) | 100 | 175 | 250 | |
Weight(kg) | 27.5 | 34 | 45.5 | |
Noise dB | 52 | 52 | 52 | |
HEPA Filter | Size | 610*610*70mm | 1170*570*70mm | 1170*1170*70mm |
Efficiency | 99.99% @0.3μm | 99.99% @0.3μm | 99.99% @0.3μm | |
Frame | High-quality aluminum | High-quality aluminum | High-quality aluminum | |
Pressure | 180pa 0.45m/s | 180pa 0.45m/s | 180pa 0.45m/s |
1. Fan filter unit description
The fan filter unit (FFU) is an air self-cleaning device that can be mounted on a ceiling or placed on a stand to achieve a local level of 100.
It can also be used to supply air at the end of a clean room. The product is equipped with an primary efficiency and high-efficiency two-stage filtration device. The fan sucks in air from the top and filters it with pre filter and hepa filter. The filtered clean air is sent out through the air outlet. There are two types of mounting methods: hanging and floor stand.
2. Fan filter unit Feature
1. Low operation cost and power consumption.
2. Built-in duct diversion system with less noise and pressure loss.
3. Filters optional: HEPA, ULPA.
4. The fan filtration unit adopts high efficient centrifugal fan to provide high air volume. High static pressure
conditions, and working life requirements up to more than 50,000 hours.
5. Suitable for use in class Class 1-1000 clean room.
6. It is especially suitable for assembling into the ultra-clean production line. It can be arranged as a single set for use according to the process requirements, or multiple sets can be connected in series to form a 100-level assembly line.